Liquid Cool
ICM-21 Interactive 3D Model
2U, 21-inch intra-chassis manifold. Brazed stainless body, five hard-wired branches, 100% pressure and helium leak tested.
About the ICM-21
ICM-21 sits inside the 21-inch, 2U liquid-cooled tray, between the chassis quick disconnects and the cold plates. A CNC-machined and brazed stainless body splits inhibited PG25 across five hard-wired branches: the centre pair feeds the ASIC and VRM cold plates, and the four outer pairs feed OSFP. The split is fixed by the internal geometry, not by valves, so there is nothing to set or drift in the field.
The cold and hot rows are isolated chambers with no cross-flow. Dry-break quick disconnects sit on the face, and options 3 and 4 add chassis BMQCs with fitted hoses, so the manifold drops into the tray as a finished assembly.
Every unit is hydrostatically proof-tested and helium leak-tested, cleaned and dried for PG25 service, and shipped capped with a serialised test record.
Parts in the 3D model
- MQDS-03 dry-break socket, cold row (4)
- MQDS-03 locking sleeve, blue (4)
- MQDS-03 port O-ring, cold row (4)
- MQDS-03 dry-break socket, hot row (4)
- MQDS-03 locking sleeve, red (4)
- MQDS-03 port O-ring, hot row (4)
- MQDS-04 dry-break socket, cold row
- MQDS-04 locking sleeve, blue
- MQDS-04 port O-ring, cold row
- MQDS-04 dry-break socket, hot row
- MQDS-04 locking sleeve, red
- MQDS-04 port O-ring, hot row
- Main body
- Bottom plate (QD face)
- End cap, hot outlet
- End cap, cold inlet
- End port barb (2)
- Ear clamp (2)
- Fitted hose, hot outlet
- Fitted hose, cold inlet
- Chassis BMQC (2)
Technical specifications
- Inlet flow
- 3–10 LPM Rated 7 LPM PG25 at 40 °C inlet
- Pressure drop
- 93 kPa At 7 LPM PG25, with BMQC
- Branches
- 5, hard-wired 1× ASIC + VRM, 4× OSFP
- Nominal split
- ≈40% / 4× ≈15% ASIC + VRM / each OSFP, ±5%, not field adjustable
- Internal volume
- 176 mL
- Coolant
- Inhibited PG25 DI water and EG mixes also acceptable
- Working, face sockets
- 7 bar MQD03/04, 20 bar burst minimum
- Working, BMQC
- 3 bar 20 bar burst minimum, blind insertion ±2.7°
- Temperature
- 0 to 80 °C Storage −20 to 80 °C, dry, ports capped
- Body
- S304L, brazed Main body + bottom plate, P/N 13002100R01
- Envelope
- 460.00 × 82.40 × 19.00 mm Length ± 0.20, across ears ± 0.20, thickness ± 0.25
- Face sockets
- 8× G1/4, 2× G3/8 4+4 MQDS-03, 1+1 MQDS-04, dry-break
- Mounting
- 10× Ø3.70 mm Through holes, ± 0.08
- Part weight
- 3.64 kg
- Leak test
- 100% pressure and helium
- Cleanliness
- No particles > 100 µm 100% drying verification
- Traceability
- Serialised test record Laser IN / OUT marks on the ends
Tutamen ICM-21 datasheet Rev 01 and tutamen.com. The datasheet governs; inspect to the ICM-21 ICD.